Advantech RS-485 Instrukcja Użytkownika Strona 143

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 142
ADAM-5000 6-21
Chapter 6
$aaSiArrff $aaSiArrff
Name RTD Configuration
Description Sets slot index, input range, data format and integration
time for a specified RTD input module in a specified
system.
Syntax $aaSiArrff(cr)
$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal
address of the ADAM-5000 system you want to
configure.
Si identifies the desired slot i (i:0to3).
A represents the I/O module configuration command.
rr represents the 2-character hexadecimal code of the
input range. (See Appendix B)
ff is a hexadecimal number that equals the 8-bit parame-
ter representing data format. Bits 0 and 1 represent data
format. Bit 7 represents integration time. The layout for
the 8-bit parameter is shown in Figure 6-3 (See page 6-
38). The other bits are not used and are set to 0. (cr) is
the terminating character, carriage return (0Dh).
Response !aa(cr) if the command is valid.
?aa(cr) if an invalid operation was entered.
There is no response if the module detects a syntax error
or communication error or if the specified address does
not exist.
! delimiter character indicating a valid command was
received.
? delimiter character indicating the command was
invalid.
aa (range 00-FF) represents the 2-character hexadecimal