6-80 ADAM-5000
Command Set
$aaSiCjAhCSkCn $aaSiCjAhCSkCn
Name Set Alarm Connection
Description Connects the High/Low alarm of the specified input
channel to the specified digital output in the addressed
ADAM-5000 system
Syntax $aaSiCjAhCSkCn(cr)
$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal
address of an ADAM-5000 system.
SiCj identifies the desired slot i (i : 0 to 3) and the
desired analog input channel j (j : 0 to 7).
AhC is the Set Alarm Connection command.
h indicates alarm type and can have the value H = High
alarm, L = Low alarm
SkCn identifies the desired slot k (k : 0 to 3) and the
desired digital output point n (n : 0 to F). To disconnect
the digital output, k and n should be set as ‘*’.
(cr) represents terminating character, carriage return
(0Dh)
Response !aa(cr) if the command was valid
There is no response if the system detects a syntax error
or communication error or if the specified address does
not exist.
! delimiter character indicating a valid command was
received.
aa represents the 2-character hexadecimal address of the
corresponding ADAM-5000 system.
(cr) represents terminating character, carriage return
(0Dh)
5013/5017/5017H/5018
Analog Input Alarm
Przeglądanie stron 201