Analog I/O Modules Calibration
6-
8
ADAM 5000 IO modules User’s Manual
Calibration resistances (ADAM-5013)
Input
Range
Code (Hex)
Input Range Span
Calibration
Resistance
Zero
Calibration
Resistance
20
Pt, -100 to 100°C A =
0.00385
140 Ohms 60 Ohms
21
Pt, 0 to 100°C A =
0.00385
140 Ohms 60 Ohms
22
Pt, 0 to 200°C A =
0.00385
200 Ohms 60 Ohms
23
Pt, 0 to 600°C A =
0.00385
440 Ohms 60 Ohms
24
Pt, -100 to 100°C A =
0.00392
140 Ohms 60 Ohms
25
Pt, 0 to 100°C A =
0.00392
140 Ohms 60 Ohms
26
Pt, 0 to 200°C A =
0.00392
200 Ohms 60 Ohms
27
Pt, 0 to 600°C A =
0.00392
440 Ohms 60 Ohms
28 Ni, -80 to 100° C 200 Ohms 60 Ohms
29 Ni, 0 to 100°C 200 Ohms 60 Ohms