C.21 Reset the calibration controller strobe —
BASE+24H
Write any values to BASE+24H to reset the calibration controller.
Table C-20 Register for reset the calibration controller strobe
Base Addr.
151413121110987654321 0
Reset the calibration controller strobe
24H W
XXXXXXXXXXXXXXXX
C.22 Change D/A channels output type strobe —
BASE+26H
Write any values to BASE+26H to change D/A channels output type.
Table C-21 Register for change D/A channels output type strobe
Base Addr.
151413121110987654321 0
Change D/A channels output type strobe
26H W
XXXXXXXXXXXXXXXX
Note:
Once you want to change the range of the specific channel, be sure to
write the value to BASE+14H first. After that, to write any value to this
register to strobe the change.