Command Set
4-30 ADAM 4000 Series User's Manual
ADAM-4055 Command Set Table
Command Syntax Command Name Command Description Page No.
%AANNTTCCFF Configuration
Sets the address, baud rate, and/or
checksum status to a digital I/O module
4-152
#AABB(data) Digital Data Out
Writes specified values to either a single
channel or all channels simultaneously
4-156
#**
Synchronized
Sampling
Orders all digital I/O modules to sample
their input values and store them in special
registers
4-158
$AA2 Configuration Status
Returns the configuration parameters of a
specified digital I/O module
4-161
$AA4
Read Synchronized
Data
Returns the value of a specified digital I/O
module that was stored in the specified
register after an #** command was issued
4-159
$AA5 Reset Status
Indicates whether a specified digital I/O
module was reset after the last time that
$AA5 command was issued
4-163
$AA6 Digital Data In
Returns the values of the digital I/O channel
in the addressed module
4-154
$AAF
Read Firmware
Ve r si o n
Return the firmware version code from the
specified digital I/O module
4-165
$AAM Read Module Name
Return the module name from the specified
digital I/O module
4-166