Advantech RS-100-RT Instrukcja Użytkownika Strona 242

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 398
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 241
4-158 ADAM 4000 Series User's Manual
Command Set
4050, 4052, 4053, 4060, 4051, 4055, 4068
#**
Name Synchronized Sampling
Description Orders all (analog or digital) input modules to sample their input
values and store them in a special register.
Syntax #**
# is a delimiter character.
** is the actual Synchronized Sampling command.
The terminating character, in the form of a carriage
return (0Dh), is not required.
Response The digital I/O modules will not respond to the Synchronized
Sampling command. In order to retrieve the data, you must
execute a Read Synchronized Data command for every module
separately.
Przeglądanie stron 241
1 2 ... 237 238 239 240 241 242 243 244 245 246 247 ... 397 398

Komentarze do niniejszej Instrukcji

Brak uwag